Telefon +36-20-344-1787, vagy E-mail: rapaskft@rapas.hu

High-voltage insulation tester Fuzrr ES3045

5, 10 (E) and 15 kV (F) versions, 10, 35 and 50 TOhm ranges, AC/DC voltage measurement, DAR, PI and capacitance measurement

ES3045  / E / F  insulation tester main features

  • DAR, PI measurement
  • Short-circuit current: >5 mA
  • DC voltage measurement range: 0 ~ 1000 V
  • AC voltage measurement range: 0 ~ 750 V
  • Capacitance measurement: 10 nF ~ 50 µF
  • Automatic discharge after measurement
  • Data storage: 500 measurement groups
  • USB interface + software
  • ES3045 series high-voltage insulation tester can be used to perform insulation testing with a measuring voltage of 5 kV (standard version), 10 kV (E), or 15 kV (F). In addition to the basic function, the device is suitable for measuring AC/DC voltage, absorption ratio, polarization index and capacitance.

    The large backlit LCD screen, the memory for storing 500 measurement data, the possibility of recalling the measured values to the display, the adjustable limit value, the USB interface and the automatic shutdown ensure convenient use. The high measurement resolution, high interference suppression, high accuracy, low weight, reliable, stable performance measuring voltage further increase the comfort of use. The device has an impact-resistant, dust-proof and moisture-proof housing.

    Specifications

     Szigetelésvizsgálat
    Range Best Resolution Accuracy
    ES3045
    Nominal measuring voltage:100V, 250V, 500V, 1000V, 2500V, 5000V ±10%
    0,01MΩ~10TΩ 0,01MΩ ±3% rdg 5 digits
    ES3045E
    Nominal measuring voltage: 250V, 500V, 1000V, 2500V, 5000V, 10KV ±10%
    0,01MΩ~35TΩ 0,01MΩ ±3% rdg  ±5 digit
    ES3045F
    Nominal measuring voltage: 500V, 1000V, 2500V, 5000V, 10KV, 15KV ±10%
    0,01MΩ~50TΩ 0,01MΩ ±3% rdg  ±5 digits
     DC feszültségmérés
    Range Resolution Accuracy
    0~1000V 0,1V ±1.5% rdg ±3 digits
     AC feszültségmérés
    Range Reesolution Accuracy
    0~750V 0,1V ±1.5% rdg ±3 digits
     Árammérés
    Range Resolution Accuracy
    0.01nA~6mA 0.01nA ±5.0% rdg ±5 digit
     Kapacitásmérés
    Range Resolution Accuracy
    10nF~50µF 10nF ±10% MÉ ±5 dtgits
    GENERAL INFORMATION
  • Output short circuit current: >6mA @15KV
  • DAR and PI measurement
  • Display: 4-digit, large, backlit LCD, 108×65 mm
  • Dimensions: H/W/H: 240 × 188 × 85mm
  • Weight: 2750 g (with battery)
  • USB interface + software
  • Alarm if the measured value is higher / lower than the set value
  • Internal memory: 500 data groups, data can be recalled to the display
  • Power supply: 12.6 V rechargeable battery
  • Depleted battery status indication: empty battery symbol
  • Energy consumption
  • Standby state: Max. 30mA (backlight off), Backlight on:
  • Max. 42mA, Measurement: 200mA max (backlight off)
  • Automatic shutdown: after 15 minutes
  • Insulation resistance: >50MΩ (between the measuring line and the housing)
  • Test voltage: AC3kV/50Hz 1 minute
  • Operating temperature / humidity: -10... +50°C, <85% RH
  • Storage temperature / humidity: -15... +55°C, <90% RH
  • Applicable standards: IEC61010-1, IEC1010-2-31, IEC61557-1.5, IEC60529(IP54), degree of pollution: 2, CAT III 300 V
  • Standard accessories

    • High voltage measuring tip with cable red 3 m, high voltage measuring wire black 1.5 m, green 1.5 m
    • USB cable + software
    • Carry bag
    • Battery charger
    • Measuring tweezers
    • Measuring hook
    • Minutes
    • User Guide